DSC-BRAIN USER GUIDE · TROUBLESHOOTING
Probe dark or faulted
Probe not reporting vs channel fault vs out of service; what steering does meanwhile; power, Wi-Fi, cable and calibration checks; judging a probe by its watering response.
● verified for 9.0.0 · firmware train 8.2.0.0
● last verified 2026-09-17 · mirrored 2026-09-15
Three different states
| Shown | Means | Steering |
|---|---|---|
| Out of service | You told the brain not to expect it | Withheld, no alert |
| Probe not reporting (warn after 15 min) | In service, no readings | Withheld; the plant reads grey; the mat loses that vote |
| Channel fault (warn) | Reporting, but a channel is frozen, railed or drifting from its peers | That channel withheld; the others still used |
A dark in-service probe reads offline, it does not vanish from the desk.
On probe firmware 8.2.0.0 every answered Modbus read marks the probe online, so a probe whose readings are moving no longer shows a standing Sensor Fault with Modbus Probe Online: off. A probe still on older firmware can show that pair while it reads normally; trust the readings and the watering response below.
Not reporting: checks
- Power and LED on the probe.
- It joined the fleet Wi-Fi: on the hub portal's Devices list, or on the ESPHome dashboard as online.
- The seat's host name or IP in Settings › Devices matches what the router gave it.
- If it just came back, the brain is in its probe back fast window; give it a minute.
Channel fault: checks
- Frozen: the sensor head is unplugged from the probe board (RS485 cable) or in air. Reseat the cable.
- Railed: a reading at a bound (moisture 100 %, EC 0). Usually a wet connector or a probe in free water.
- Drifting from peers: compare with the other probe in similar substrate. Run Soft calibrate (tap water → after water) or a Lab wet calibration if EC or pH is off by a constant.
Judge by the watering response
A probe is good if moisture steps up on a watering and dries back over the following days. Fault flags describe a moment; the response describes the probe. Log a Water entry and watch the Dryback chart (the probe shows READING FAST for a while after a logged watering).
Replacing
Flash the replacement with the same role, update the seat's host, recalibrate. The plant keeps its slot and journal.
DSC-Brain user guide · Probe dark or faulted · this page is edited on the site; the Notion original was retired after the mirror